How can I directly control in RMS simulation the active (P) and reactive (Q) power of a single phase (1-phase) Static Generator (ElmGenstat)?

Category:
Dynamic Simulation
Answer

The attached example provides a simple network where one single phase static generator (converter) is directly being controlled via DSL to set the output active and reactive power (constant power model). As with any constant PQ models, this example is suitable for RMS simulations where voltages are always within the normal operating region. Whenever transient studies are to be investigated, this model is not recommended to be used, instead either a controlled current or voltage source should be employed.