How do I change the inductance and resistance of a series reactor (inductor) during an EMT simulation?

Category:
Power Equipment Models
Answer

In order to modify the inductance and resistance of the Series Reactor element within an EMT simulation, then the following signals must be set externally from a user defined model (e.g. DSL or Modelica): Lin_A,Lin_B,Lin_C,Rin_A,Rin_B,Rin_C.

An example is provided attached, where a DSL model is built to set the required inputs signals, with values based on internally defined look-up arrays (IntMat) stored within the DSL model (ElmDsl).

 

Further tags: variable/adjustable resistance/reactance/inductance